UL 1032/CSA TR-32High Voltage Hook-up Wire

   Figure
                 
1.Conductor
         Annealed Copper Wire(Bare Single,Tinned Single, Tinned Strand,or Top-Tinned Strand)
2.Insulation PVC (Polyvinyl  Chloride)
3.Structure

Conductor

Insulation

Conductor  
Resistance
(20)

AWG

Construction

Diameter

Min  
Thickness

Nominal  
Thickness

Diameter

24

11 / 0.16TA

approx.0.61 mm

 0.686 mm

0.795 mm

2.20 ± 0.10 mm

85.49W / Km

24

7 / 0.20TA

approx.0.60 mm

0.80 mm

2.20 ± 0.10 mm

85.95W / Km

22

17 / 0.16TA

approx.0.76 mm

0.82 mm

2.40 ± 0.10 mm

59.74W / Km

22

7 / 0.26TA

approx.0.78 mm

0.81 mm

2.40 ± 0.10 mm

54.79W / Km

20

21 / 0.18TA

approx.0.95 mm

0.875 mm

2.70 ± 0.10 mm

38.46W / Km

20

7 / 0.32TA

approx.0.96 mm

0.87 mm

2.70 ± 0.10 mm

34.12W / Km

20

10 / 0.26TA

approx.0.95 mm

0.875 mm

2.70 ± 0.10 mm

38.71W / Km

18

34 / 0.18TA

approx.1.20 mm

0.845 mm

2.90 ± 0.10 mm

24.70W / Km

20

1 / 0.813TA

approx.0.813 mm

0.843 mm

2.50 ± 0.10 mm

35.20W / Km

22

7 / 0.26ATC

approx.0.76 mm

0.81 mm

2.40 ± 0.10 mm

57.30W / Km

              ABare Copper       BTinned Copper   ATCTop-Tinned Strand

4.Characteristics

Items

Specification

Rating

90 1000V(AC) 1200V(DC)

Dielectric Strength

AC 3000V / min.

Insulation Resistance

Min. 10MW - Km (20) at DC 500V

Flame Test

ULVW-1  CSAFT-1

Elongation of Insulation

Min.100

Tensile Strength of Insulation

Min.1.05Kg / mm2

Residual of Elongation after Aging

 Min. 65 of original (113℃,168H)

Residual of Tensile Strength after Aging

 Min. 70 of original (113℃,168H) 

5.MarkingE54979 AWM  1032  VW - 1  1000V (AC)  1200V(DC)  90  AWG 
            TATUNG  LL58500  CSA  TR - 32  FT1  - F -